[BS] A206.7 Anchorage at Interior Walls
JUMP TO FULL CODE CHAPTER
Existing interior reinforced concrete or reinforced masonry walls that extend to the floor above or to the roof diaphragm shall be anchored for out-of-plane forces per Sections A206.1 and A206.3. Walls extending through the roof diaphragm shall be anchored for out-of-plane forces on both sides, and continuity ties shall be spliced across or continuous through the interior wall to provide diaphragm continuity.
Related Code Sections
A206.7 Guidelines for the Seismic Retrofit of Existing Buildings, Anchorage at Interior Walls
Existing interior reinforced concrete or reinforced masonry walls that extend to the floor above or to the roof diaphragm shall be anchored for out ...
2020 Existing Building Code of NYS > A Guidelines for the Seismic Retrofit of Existing Buildings > A206 Analysis and Design > A206.7 Anchorage at Interior Walls
A206.7 Earthquake Hazard Reduction in Existing Reinforced Concrete and Reinforced Masonry Wall Buildings With Flexible Diaphragms, Anchorage at Interior Walls
Existing interior reinforced concrete or reinforced masonry walls that extend to the floor above or to the roof diaphragm shall be anchored for out ...
Existing Building Code 2015 of New York State > A2 Earthquake Hazard Reduction in Existing Reinforced Concrete and Reinforced Masonry Wall Buildings With Flexible Diaphragms > A206 Analysis and Design > A206.7 Anchorage at Interior Walls
1705.12.5 Special Inspections and Tests, Architectural Components
Periodic special inspection is required for the erection and fastening of exterior cladding, interior and exterior nonbearing walls and interior ...
Building Code 2015 of New York State > 17 Special Inspections and Tests > 1705 Required Special Inspections and Tests > 1705.12 Special Inspections for Seismic Resistance > 1705.12.5 Architectural Components
1705.12.5 Special Inspections and Tests, Architectural Components
Periodic special inspection is required for the erection and fastening of exterior cladding, interior and exterior nonbearing walls and interior ...
2020 Building Code of New York State > 17 Special Inspections and Tests > 1705 Required Special Inspections and Tests > 1705.12 Special Inspections for Seismic Resistance > 1705.12.5 Architectural Components
2109.7 Masonry, Anchorage
Interior nonload-bearing walls shall be anchored at their intersection, at vertical ...