3104F.2.3 Analytical Procedures
The objective of the seismic analysis is to verify that the displacement capacity of the structure is greater than the displacement demand, for each performance level defined in Table 31F-4-1. For this purpose, the displacement capacity of each element of the structure shall be checked against its displacement demand including the orthogonal effects of Section 3104F.4.2. The required analytical procedures are summarized in Table 31F-4-2.
The displacement capacity of the structure shall be calculated using the nonlinear static (pushover) procedure. For the nonlinear static (pushover) procedure, the push-over load shall be applied at the target node defined as the center of mass (CM) of the MOT structure. It is also acceptable to use a nonlinear dynamic procedure for capacity evaluation, subject to peer review in accordance with Section 3101F.8.2.
Methods used to calculate the displacement demand are linear modal, nonlinear static and nonlinear dynamic.
Mass to be included in the displacement demand calculation shall include mass from self-weight of the structure, weight of the permanent equipment, and portion of the live load that may contribute to inertial mass during earthquake loading, such as a minimum of 25% of the floor live load in areas used for storage.
Any rational method, subject to the Division's approval, can be used in lieu of the required analytical procedures shown in Table 31F-4-2.
To assess displacement capacity, two-dimensional nonlinear static (pushover) analyses shall be performed; three-dimensional analyses are optional. A model that incorporates the nonlinear load deformation characteristics of all components for the lateral force-resisting system shall be used in the pushover analysis.
Alternatively, displacement capacity of a pile in the MOT structure may be estimated from pushover analysis of an individual pile with appropriate axial load and pile-to-deck connection.
The displacement capacity of a pile from the push-over analysis shall be defined as the displacement that can occur at the top of the pile without exceeding plastic rotation (or material strain) limits, either at the pile-deck hinge or in-ground hinge, as defined in Section 3107F. If pile displacement has components along two axes, as may be the case for irregular MOTs, the pile displacement capacity shall be defined as the resultant of its displacement components along the two axes.
A series of nonlinear pushover analyses may be required depending on the complexity of the MOT structure. At a minimum, pushover analysis of a two-dimensional model shall be conducted in both the longitudinal and transverse directions. The piles shall be represented by nonlinear elements that capture the moment-curvature/rotation relationships for components with expected inelastic behavior in accordance with Section 3107F. The effects of connection flexibility shall be considered in pile-to-deck connection modeling. For prestressed concrete piles, Figure 31F-4-2 may be used. A nonlinear element is not required to represent each pile location. Piles with similar lateral force-deflection behavior may be lumped in fewer larger springs, provided that the overall torsional effects are captured.
Linear material component behavior is acceptable where nonlinear response will not occur. All components shall be based on effective moment of inertia calculated in accordance with Section 3107F. Specific requirements for timber pile structures are discussed in the next section.
PILE-DECK CONNECTION MODELING FOR PRESTRESSED CONCRETE PILE (ADAPTED FROM [4.2])
For all timber pile supported structures, linear elastic procedures may be used. Alternatively, the nonlinear static procedure may be used to estimate the target displacement demand, Δd.
A simplified single pile model for a typical timber pile supported structure is shown in Figure 31F-4-3. The pile-deck connections may be assumed to be "pinned." The lateral bracing can often be ignored if it is in poor condition. These assumptions shall be used for the analysis, unless a detailed condition assessment and lateral analysis indicate that the existing bracing and connections may provide reliable lateral resistance.
A series of single pile analyses may be sufficient to establish the nonlinear springs required for the pushover analysis.
SIMPLIFIED SINGLE PILE MODEL OF A TIMBER PILE SUPPORTED STRUCTURE
A nonlinear static procedure shall be used to determine the displacement demand for all concrete and steel structures, with the exception of irregular configurations with high or moderate spill classifications. A linear modal procedure is required for irregular structures with high or moderate spill classifications, and may be used for all other classifications in lieu of the nonlinear static procedure.
In the nonlinear static demand procedure, deformation demand in each element shall be computed at the target node displacement demand. The analysis shall be conducted in each of the two orthogonal directions and results combined as described in Section 3104F.4.2.
The target displacement demand of the structure, Δd, shall be calculated by multiplying the spectral response acceleration, SA, corresponding to the effective elastic structural period, Te (see Equation (4-2) or Equation (4-8)), by . If Te < T0, where T0 is the period corresponding to the peak of the acceleration response spectrum, a refined analysis (see Section 3104F.2.3.2.1 or 3104F.2.3.2.2) shall be used to calculate the displacement demand. In the refined analysis, the target node displacement demand may be computed from the Coefficient Method of ASCE/SEI 41 [4.3] that is based on the procedure presented in FEMA 440 [4.6], or the Substitute Structure Method presented in Priestley et al. [4.4]. Both of these methods utilize the pushover curve developed in Section 3104F.2.3.1.
The Coefficient Method is based on the ASCE/SEI 41 [4.3] procedure.
The first step in the Coefficient Method requires idealization of the pushover curve to calculate the effective elastic lateral stiffness, ke, and effective yield strength, Fy, of the structure as shown in Figure 31F-4-4.
The first line segment of the idealized pushover curve shall begin at the origin and have a slope equal to the effective elastic lateral stiffness, ke. The effective elastic lateral stiffness, ke, shall be taken as the secant stiffness calculated at the lateral force equal to 60 percent of the effective yield strength, Fy, of the structure. The effective yield strength, Fy, shall not be taken as greater than the maximum lateral force at any point along the pushover curve.
The second line segment shall represent the positive post-yield slope (α1ke) determined by a point (Fd,Δd) and a point at the intersection with the first line segment such that the area above and below the actual curve area approximately balanced. (Fd,Δd) shall be a point on the actual pushover curve at the calculated target displacement, or at the displacement corresponding to the maximum lateral force, whichever is smaller.
The third line segment shall represent the negative post-yield slope (α2ke), determined by the point at the end of the positive post-yield slope (Fd, Δd) and the point at which the lateral force degrades to 60 percent of the effective yield strength.
The target displacement shall be calculated from:
(4-1)
where:
SA = spectral acceleration of the linear-elastic system at vibration period, which is computed from:
(4-2)
where:
m | = | seismic mass as defined in Section 3104F.2.3 |
ke | = | effective elastic lateral stiffness from idealized pushover |
C1 | = | modification factor to relate maximum inelastic displacement to displacement calculated for linear elastic response. For period less than 0.2 s, C1 need not be taken greater than the value at Te = 0.2 s. For period greater than 1.0 s, C1 = 1.0. For all other periods: |
(4-3)
where:
α | = | Site class factor |
= | 130 for Site Class A or B, | |
= | 90 for Site Class C, and | |
= | 60 for Site Class D, E, or F. | |
μstrength | = | ratio of elastic strength demand to yield strength coefficient calculated in accordance with Equation (4-5). The Coefficient Method is not applicable where μstrength exceeds μmax computed from Equation (4-6). |
C2 | = | modification factor to represent the effects of pinched hysteresis shape, cyclic stiffness degradation, and strength deterioration on the maximum displacement response. For periods greater than 0.7s, C2 = 1.0. For all other periods: |
(4-4)
The strength ratio μstrength shall be computed from:
(4-5)
where:
Fy = yield strength of the structure in the direction under consideration from the idealized pushover curve.
For structures with negative post-yield stiffness, the maximum strength ratio μmax shall be computed from:
(4-6)
where:
Δd = larger of target displacement or displacement corresponding to the maximum pushover force,
Δy = displacement at effective yield strength
h = 1 + 0.15lnTe, and
αe = effective negative post-yield slope ratio which shall be computed from:
(4-7)
where:
αP-Δ, and the maximum negative post-elastic stiffness ratio, α2, are estimated from the idealized force-deformation curve, and λ is a near-field effect factor equal to 0.8 for sites with 1 second spectral value, S1 greater than or equal to 0.6g and equal to 0.2 for sites with 1 second spectral value, S1 less than 0.6g.
IDEALIZATION OF PUSHOVER CURVE (ADAPTED FROM [4.3])
The Substitute Structure Method is based on the procedure presented in Priestley et al. [4.4] and is briefly summarized below.
- Idealize the pushover curve from nonlinear pushover analysis, as described in Section 3104F.2.3.2.1, and estimate the yield force, Fy, and yield displacement, Δy.
- Compute the effective elastic lateral stiffness, ke, as the yield force, Fy, divided by the yield displacement, Δy.
Compute the structural period in the direction under consideration from:
(4-8)
where:
m =seismic mass as defined in Section 3104F.2.3
ke =effective elastic lateral stiffness in direction under consideration
Determine target displacement Δd, from:
(4-9)
SA = spectral displacement corresponding tostructural period, Te
The ductility level,μΔ, is found from Δd /Δy. Use the appropriate relationship between ductility and damping, for the component undergoing inelastic deformation, to estimate the effective structural damping, ξeff. In lieu of more detailed analysis, the relationship shown in Figure 31F-4-5 or Equation (4-10) may be used for concrete and steel piles connected to the deck through dowels embedded in the concrete.
(4-10)
where:
r =ratio of second slope over elastic slope (see Figure 31F-4-7)
Equation (4-10) for effective damping was developed by Kowalsky et al. [4.5] for the Takeda hysteresis model of system's force-displacement relationship.
From the acceleration response spectra, create elastic displacement spectra, SD, using Equation (4-11) for various levels of damping.
(4-11)
- Using the curve applicable to the effective structural damping, ξeff, find the effective period, Td (see Figure 31F-4-6).
- In order to convert from a design displacement response spectra to another spectra for a different damping level, the adjustment factors in Section 3103F.4.2.9 shall be used.
The effective secant stiffness, keff, can then be found from:
(4-12)
where:
m = seismic mass as defined in Section 3104F.2.3
Td = effective structural period
The required strength, Fu, can now be estimated by:
(4-13)
- Fu and Δd can be plotted on the force-displacement curve established by the pushover analysis. Since this is an iterative process, the intersection of Fu and Δd most likely will not fall on the force-displacement curve and a second iteration will be required. An adjusted value of Δd, taken as the intersection between the force-displacement curve and a line between the origin and Fu and Δd, can be used to find μΔ.
- Repeat the process until a satisfactory solution is obtained (see Figure 31F-4-7).
- From pushover data, calculate the displacement components of an element along the two axis of the system.
RELATION BETWEEN DUCTILITY, μΔ, AND EFFECTIVE DAMPING, ξeff [4.5]
DESIGN DISPLACEMENT RESPONSE SPECTRA
EFFECTIVE LATERAL STIFFNESS (ADAPTED FROM [4.4])