• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

Section 422 Ambulatory Care Faciilities

Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 422 Ambulatory Care Faciilities
JUMP TO FULL CODE CHAPTER

422.1 General

Occupancies classified as ambulatory care facilities shall comply with the provisions of Sections 422.1 through 422.7 and other applicable provisions of this code.

422.2 Separation

CALCULATE P
P Premium Feature

This feature is included in premium subscriptions only. Click below to start a free trial.

Start Free Trial
CALCULATE
Calculate code sheet portions referencing this topic.
Ambulatory care facilities where the potential for four or more care recipients are to be incapable of self-preservation at any time shall be separated from adjacent spaces, corridors or tenants with a fire partition installed in accordance with Section 708.

422.3 Smoke Compartments

Where the aggregate area of one or more ambulatory care facilities is greater than 10,000 square feet (929 m2) on one story, the story shall be provided with a smoke barrier to subdivide the story into not fewer than two smoke compartments. The area of any one such smoke compartment shall be not greater than 22,500 square feet (2092 m2). The distance of travel from any point in a smoke compartment to a smoke barrier door shall be not greater than 200 feet (60 960 mm). The smoke barrier shall be installed in accordance with Section 709 with the exception that smoke barriers shall be continuous from outside wall to an outside wall, a floor to a floor, or from a smoke barrier to a smoke barrier or a combination thereof.

422.3.1 Means of Egress

Where ambulatory care facilities require smoke compartmentation in accordance with Section 422.3, the fire safety evacuation plans provided in accordance with Section 1002.2 shall identify the building components necessary to support a defend-in-place emergency response in accordance with Sections 403 and 404 of the International Fire Code.

422.3.2 Refuge Area

Not less than 30 net square feet (2.8 m2) for each nonambulatory care recipient shall be provided within the aggregate area of corridors, care recipient rooms, treatment rooms, lounge or dining areas and other low-hazard areas within each smoke compartment. Each occupant of an ambulatory care facility shall be provided with access to a refuge area without passing through or utilizing adjacent tenant spaces.

422.3.3 Independent Egress

CALCULATE P
P Premium Feature

This feature is included in premium subscriptions only. Click below to start a free trial.

Start Free Trial
CALCULATE
Calculate code sheet portions referencing this topic.
A means of egress shall be provided from each smoke compartment created by smoke barriers without having to return through the smoke compartment from which means of egress originated.

[F] 422.4 Automatic Sprinkler Systems

ILLUSTRATION
Automatic sprinkler systems shall be provided for ambulatory care facilities in accordance with Section 903.2.2.

[F] 422.5 Fire Alarm Systems

A fire alarm system shall be provided for ambulatory care facilities in accordance with Section 907.2.2.

[F] 422.6 Electrical Systems

In ambulatory care facilities, the essential electrical system for electrical components, equipment and systems shall be designed and constructed in accordance with the provisions of Chapter 27 and NFPA 99.

422.7 Domestic Cooking

Installation of cooking appliances used in domestic cooking facilities shall comply with all of the following:
  1. The types of cooking appliances permitted are limited to ovens, cooktops, ranges, warmers and microwaves.
  2. Domestic cooking hoods installed and constructed in accordance with Section 505 of the International Mechanical Code shall be provided over cooktops or ranges.
  3. A shutoff for the fuel and electrical supply to the cooking equipment shall be provided in a location to which only staff has access.
  4. A timer shall be provided that automatically deactivates the cooking appliances within a period of not more than 120 minutes.
  5. A portable fire extinguisher shall be provided. Installation shall be in accordance with Section 906 and the extinguisher shall be located within a 30-foot (9144 mm) distance of travel from each domestic cooking appliance.

Related Code Sections


Section 422 Special Detailed Requirements Based on Occupancy and Use, Ambulatory Care Faciilities
Occupancies classified as ambulatory care facilities shall comply with the provisions of Sections 422.1 through 422.7 and other applicable provisions ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 422 Ambulatory Care Faciilities
Section 422 Special Detailed Requirements Based on Occupancy and Use, Ambulatory Care Faciilities
Occupancies classified as ambulatory care facilities shall comply with the provisions of Sections 422.1 through 422.6 and other applicable provisions ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 422 Ambulatory Care Faciilities
422.5 Special Detailed Requirements Based on Occupancy and Use, Fire Alarm Systems
A fire alarm system shall be provided for ambulatory care facilities in accordance with Section 907.2.2 ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 422 Ambulatory Care Faciilities > 422.5 Fire Alarm Systems
422.3 Special Detailed Requirements Based on Occupancy and Use, Smoke Compartments
Where the aggregate area of one or more ambulatory care facilities is greater than 10,000 square feet (929 m2) on one story, the story shall ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 422 Ambulatory Care Faciilities > 422.3 Smoke Compartments
422.3 Special Detailed Requirements Based on Occupancy and Use, Smoke Compartments
Where the aggregate area of one or more ambulatory care facilities is greater than 10,000 square feet (929 m2) on one story, the story shall ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 422 Ambulatory Care Faciilities > 422.3 Smoke Compartments
Help Contact Us Privacy Terms
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code Compare
Code Compare
Highlight differences between any two building codes.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING