11.12.3.2.5 Alternative Setbacks at Ridge
Fire Code 2021 of West Virginia > 11 Building Services > 11.12 Photovoltaic Systems > 11.12.2 Building-Mounted Photovoltaic (PV) and Building Integrated Photovoltaic (BIPV) Installations > 11.12.3 Rooftop Access and Ventilation > 11.12.3.2 One- And Two-Family Dwellings and Townhouses > 11.12.3.2.5 Alternative Setbacks at Ridge
Go To Full Code Chapter
11.12.3.2.5.1
For one- and two-family dwellings with an automatic sprinkler system installed within the dwelling in accordance with 13.3.2.19, for PV arrays occupying up to 66 percent
of the plan view roof area, a minimum 18 in. (457 mm) setback
shall be provided on either side of a horizontal ridge.
11.12.3.2.5.2
For PV arrays occupying more than 66 percent
of the plan view roof area on sprinklered one- and two-family
dwellings, a minimum 36 in. (914 mm) setback shall be provided on either side of a horizontal ridge.
Related Code Sections
11.12.3.2.5 Building Services, Alternative Setbacks at Ridge
occupying up to 66 percent
of the plan view roof area, a minimum 18 in. (457 mm) setback
shall be provided on either side of a horizontal ridge ...
Fire Code 2021 of West Virginia > 11 Building Services > 11.12 Photovoltaic Systems > 11.12.2 Building-Mounted Photovoltaic (PV) and Building Integrated Photovoltaic (BIPV) Installations > 11.12.3 Rooftop Access and Ventilation > 11.12.3.2 One- And Two-Family Dwellings and Townhouses > 11.12.3.2.5 Alternative Setbacks at Ridge
R324.6.2.1 Building Planning, Alternative Setback at Ridge
Where an automatic sprinkler system is installed within the dwelling in accordance with NFPA 13D or Section P2904, setbacks at ridges shall comply ...
1803.5.10 Soils and Foundations, Alternate Setback and Clearance
Where setbacks or clearances other than those required in Section 1808.7 are desired, the building official shall be permitted to require ...
1803.5.10 Soils and Foundations, Alternate Setback and Clearance
Where setbacks or clearances other than those required in Section 1808.7 are desired, the building official shall be permitted to require ...
1808.7.5 Soils and Foundations, Alternate Setback and Clearance
Alternate setbacks and clearances are permitted, subject to the approval of the building official. The building official shall be permitted ...