705.8.1 Allowable Area of Openings
JUMP TO FULL CODE CHAPTER
The maximum area of unprotected and protected openings permitted in an exterior wall in any story of a building shall not exceed the percentages specified in Table 705.8.
Exceptions:
- In other than Group H occupancies, unlimited unprotected openings are permitted in the first story above grade plane either:
- Where the wall faces a street and has a fire separation distance of more than 15 feet (4572 mm); or
- Where the wall faces an unoccupied space. The unoccupied space shall be on the same lot or dedicated for public use, shall not be less than 30 feet (9144 mm) in width and shall have access from a street by a posted fire lane in accordance with the Florida Fire Prevention Code.
- Buildings whose exterior bearing walls, exterior nonbearing walls and exterior primary structural frame are not required to be fire-resistance rated shall be permitted to have unlimited unprotected openings.
Related Code Sections
705.8.1 Fire and Smoke Protection Features, Allowable Area of Openings
The maximum area of unprotected and protected openings permitted in an exterior wall in any story of a building shall not exceed the percentages ...
2014 FBC - Building, 5th edition > 7 Fire and Smoke Protection Features > 705 Exterior Walls > 705.8 Openings > 705.8.1 Allowable Area of Openings
705.8.1 Fire and Smoke Protection Features, Allowable Area of Openings
The maximum area of unprotected and protected openings permitted in an exterior wall in any story of a building shall not exceed the percentages ...
2017 FBC - Building, 6th edition > 7 Fire and Smoke Protection Features > 705 Exterior Walls > 705.8 Openings > 705.8.1 Allowable Area of Openings
705.8.1 Fire and Smoke Protection Features, Allowable Area of Openings
The maximum area of unprotected and protected openings permitted in an exterior wall in any story of a building shall not exceed the percentages ...
2020 FBC - Building, 7th edition > 7 Fire and Smoke Protection Features > 705 Exterior Walls > 705.8 Openings > 705.8.1 Allowable Area of Openings
513.5.1 Exhaust Systems, Total Leakage Area
Total leakage area of the barrier is the product of the smoke barrier gross area times the allowable leakage area ratio, plus the area of other ...
2017 FBC - Mechanical, 6th edition > 5 Exhaust Systems > 513 Smoke Control Systems > 513.5 Smoke Barrier Construction > 513.5.1 Total Leakage Area
513.5.1 Exhaust Systems, Total Leakage Area
Total leakage area of the barrier is the product of the smoke barrier gross area times the allowable leakage area ratio, plus the area of other ...
2020 FBC - Mechanical, 7th edition > 5 Exhaust Systems > 513 Smoke Control Systems > 513.5 Smoke Barrier Construction > 513.5.1 Total Leakage Area