1017.3 Aisle Accessways in Group M
JUMP TO FULL CODE CHAPTER
An aisle accessway shall be provided on at least one side of each element within the merchandise pad. The minimum clear width for an aisle accessway not required to be accessible shall be 30 inches (762 mm). The required clear width of the aisle accessway shall be measured perpendicular to the elements and merchandise within the merchandise pad. The 30-inch (762 mm) minimum clear width shall be maintained to provide a path to an adjacent aisle or aisle accessway. The common path of travel shall not exceed 30 feet (9144 mm) from any point in the merchandise pad.
Exception: For areas serving not more than 50 occupants, the common path of travel shall not exceed 75 feet (22 880 mm).
Exception: For areas serving not more than 50 occupants, the common path of travel shall not exceed 75 feet (22 880 mm).
Related Code Sections
1017.3 Means of Egress, Aisle Accessways in Group M
An aisle accessway shall be provided on at least one side of each element within the merchandise pad. The minimum clear width for an aisle accessway ...
1017.4.2 Means of Egress, Table and Seating Accessway Width
Aisle accessways shall provide a minimum of 12 inches (305 mm) of width plus 1 / 2 inch (12.7 mm) of width for each additional 1 foot (305 mm ...
NYC Building Code 2014 > 10 Means of Egress > 1017 Aisles > 1017.4 Seating at Tables > 1017.4.2 Table and Seating Accessway Width
1017.4 Means of Egress, Seating at Tables
Where seating is located at a table or counter and is adjacent to an aisle or aisle accessway, the measurement of required clear width of the aisle ...
1013.4.2 Means of Egress, Seating at Tables
Where seating is located at a table or counter and is adjacent to an aisle or aisle accessway, the measurement of the minimum aisle width shall start ...
NYC Building Code 2008 > 10 Means of Egress > 1013 Exit Access > 1013.4 Aisles > 1013.4.2 Seating at Tables