[F] 907.2.22.1 Airport Traffic Control Towers With Multiple Exits and Automatic Sprinklers
JUMP TO FULL CODE CHAPTER
Airport traffic control towers with multiple exits and equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 shall be provided with smoke detectors in all of the following locations:
- Airport traffic control cab.
- Electrical and mechanical equipment rooms.
- Airport terminal radar and electronics rooms.
- Outside each opening into interior exit stairways.
- Along the single means of egress permitted from observation levels.
- Outside each opening into the single means of egress permitted from observation levels.
Related Code Sections
907.2.21.1 Fire Protection and Life Safety Systems, Airport Traffic Control Towers With Multiple Exits and Automatic Sprinklers
Airport traffic control towers with multiple exits and equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.21 Airport Traffic Control Towers > 907.2.21.1 Airport Traffic Control Towers With Multiple Exits and Automatic Sprinklers
907.2.22.1 Fire Protection and Life Safety Systems, Airport Traffic Control Towers With Multiple Exits and Automatic Sprinklers
Airport traffic control towers with multiple exits and equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 ...
Building Code 2021 of Illinois > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.22 Airport Traffic Control Towers > 907.2.22.1 Airport Traffic Control Towers With Multiple Exits and Automatic Sprinklers
412.2 Special Detailed Requirements Based on Occupancy and Use, Airport Traffic Control Towers
The means of egress in airport traffic control towers shall comply with Sections 412.2.2.1 ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 412 Aircraft-Related Occupancies > 412.2 Airport Traffic Control Towers
412.2 Special Detailed Requirements Based on Occupancy and Use, Airport Traffic Control Towers
Where an airport traffic control tower is equipped throughout with an automatic sprinkler system in accordance with Section ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 412 Aircraft-Related Occupancies > 412.2 Airport Traffic Control Towers
412.2.2.3 Special Detailed Requirements Based on Occupancy and Use, Number of Exits
traffic control tower is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and two exits are required ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 412 Aircraft-Related Occupancies > 412.2 Airport Traffic Control Towers > 412.2.2 Means of Egress and Evacuation > 412.2.2.3 Number of Exits