2006.12 Aircraft Engines and Heaters
JUMP TO FULL CODE CHAPTER
Operation of aircraft onboard engines and combustion heaters shall be terminated prior to commencing fuel service operations and shall remain off until the fuel-servicing operation is completed.
Exception: In an emergency, a single jet engine is allowed to be operated during fuel servicing where all of the following conditions are met:
- The emergency shall have resulted from an onboard failure of the aircraft's auxiliary power unit.
- Restoration of auxiliary power to the aircraft by ground support services is not available.
- The engine to be operated is either at the rear of the aircraft or on the opposite side of the aircraft from the fuel service operation.
- The emergency operation is in accordance with a written procedure approved by the fire code official.
Related Code Sections
2006.12 Aviation Facilities, Aircraft Engines and Heaters
Operation of aircraft onboard engines and combustion heaters shall be terminated prior to commencing fuel-servicing operations and shall remain off ...
Fire Code 2021 of Colorado > 20 Aviation Facilities > 2006 Aircraft Fueling > 2006.12 Aircraft Engines and Heaters
2006.12 Aviation Facilities, Aircraft Engines and Heaters
Operation of aircraft onboard engines and combustion heaters shall be terminated prior to commencing fuel service operations and shall remain off ...
Fire Code 2018 of Colorado > 20 Aviation Facilities > 2006 Aircraft Fueling > 2006.12 Aircraft Engines and Heaters
412.3.4 Special Detailed Requirements Based on Occupancy and Use, Heating Equipment
of wings or engine enclosures of the highest aircraft that are permitted to be housed in the hangar need not be located in a separate room provided ...
Building Code 2021 of Colorado > 4 Special Detailed Requirements Based on Occupancy and Use > 412 Aircraft-Related Occupancies > 412.3 Aircraft Hangars > 412.3.4 Heating Equipment
412.3.4 Special Detailed Requirements Based on Occupancy and Use, Heating Equipment
of wings or engine enclosures of the highest aircraft that are permitted to be housed in the hangar need not be located in a separate room provided ...
Building Code of the Department of Personnel & Administration/Office of the State Architect (DPA/OSA) > 4 Special Detailed Requirements Based on Occupancy and Use > 412 Aircraft-Related Occupancies > 412.3 Aircraft Hangars > 412.3.4 Heating Equipment
412.4.4 Special Detailed Requirements Based on Use and Occupancy, Heating Equipment
surface of wings or engine enclosures of the highest aircraft that are permitted to be housed in the hangar need not be located in a separate room ...
Building Code of the Department of Personnel & Administration/Office of the State Architect (DPA/OSA) > 4 Special Detailed Requirements Based on Use and Occupancy > 412 Aircraft-Related Occupancies > 412.4 Aircraft Hangars > 412.4.4 Heating Equipment