// CODE SNIPPET
608.1 Air-Moving Systems and Smoke Detectors
Go To Full Code Chapter
Air-moving systems supplying air in excess of 2000 cubic feet per minute (ft3/min) (0.9439 m3/s) to enclosed spaces within buildings shall be equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the air-moving equipment upon detection of smoke in the main supply-air duct served by such equipment. Duct smoke detectors shall comply with UL 268A and shall be installed in accordance with the manufacturer's installation instructions. Such devices shall be compatible with the operating velocities, pressures, temperatures, and humidities of the system. Where fire-detection or alarm systems are provided for the building, the smoke detectors shall be supervised by such systems in an approved manner.
Exceptions:
- Where the space supplied by the air-moving equipment is served by a total coverage smoke-detection system in accordance with the fire code, interconnection to such system shall be permitted to be used to accomplish the required shutoff.
- Automatic shutoff is not required where occupied rooms served by the air-handling equipment have direct exit to the exterior, and the travel distance does not exceed 100 feet (30 480 mm).
- Automatic shutoff is not required for Group R, Division 3 and Group U Occupancies.
- Automatic shutoff is not required for approved smoke-control systems or where analysis demonstrates shutoff would create a greater hazard, such as shall be permitted to be encountered in air-moving equipment supplying specialized portions of Group H Occupancies. Such equipment shall be required to have smoke detection with remote indication and manual shutoff capability at an approved location.
- Smoke detectors that are factory installed in listed air-moving equipment shall be permitted to be used in lieu of smoke detectors installed in the main supply-air duct served by such equipment.
Upcodes Diagrams
Related Code Sections
608.1 Duct Systems, Air-Moving Systems and Smoke Detectors
in an approved manner.
Exceptions:
Where the space supplied by the air-moving equipment is served by a total coverage smoke-detection system in accordance ...
909.20.4 Fire Protection Systems, Mechanical Ventilation Alternative
simultaneously. Smoke detectors shall be located at the floor-side entrance to each vestibule and shall activate the system for the affected vestibule ...
907.2.18.1 Fire Protection Systems, Smoke Detectors
that in Group R occupancies, a listed smoke detector is allowed to be used in each return air riser carrying not more than 5,000 cfm (2.4 m3/s) and serving ...
909.20.4 Fire Protection and Life Safety Systems, Mechanical Ventilation Alternative
three vestibules simultaneously. Smoke detectors shall be located at the floor-side entrance to each vestibule and shall activate the system ...
907.2.17.1 Fire Protection and Life Safety Systems, Smoke Detectors
occupancies, a listed smoke detector is allowed to be used in each return air riser carrying not more than 5,000 cfm (2.4 m3/s) and serving not more than 10 ...