702.3 Air From Adjacent Spaces
JUMP TO FULL CODE CHAPTER
Where the volume of the room in which the fuel-burning appliances are located does not comply with Section 702.2, additional inside combustion and dilution air shall be obtained by opening the room to adjacent spaces so that the combined volume of all communicating spaces meets the volumetric requirement of Section 702.2. Openings connecting the spaces shall comply with Sections 702.3.1, 702.3.2 and Figure A-1 of Appendix A of this code.
Two openings shall be provided, one within 1 foot (305 mm) of the ceiling of the room and one within 1 foot (305 mm) of the floor.
The net free area of each opening, calculated in accordance with Section 708, shall be a minimum of 1 square inch per 1,000 Btu/h (2201 mm2/kW) of input rating of the fuel-burning appliances drawing combustion and dilution air from the communicating spaces and shall be not less than 100 square inches (64 516 mm2).
Related Code Sections
702.3 Combustion Air, Air From Adjacent Spaces
and dilution air shall be obtained by opening the room to adjacent spaces so that the combined volume of all communicating spaces meets the volumetric ...
702.3 Combustion, Ventilation, and Dilution Air, Air From Adjacent Spaces
, ventilation, and dilution air shall be obtained by opening the room to adjacent spaces so that the combined volume of all communicating spaces meets ...
NYC Mechanical Code 2014 > 7 Combustion, Ventilation, and Dilution Air > 702 Inside Air > 702.3 Air From Adjacent Spaces
409.3.1 Special Detailed Requirements Based on Use and Occupancy, Supply Air
the outside; from adjacent spaces within the building, provided the volume and infiltration rate is sufficient; or from the building air-conditioning system ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 409 Motion Picture Projection Rooms > 409.3 Projection Room and Equipment Ventilation > 409.3.1 Supply Air
409.3.1.1 Special Detailed Requirements Based on Use and Occupancy, Supply Air
the outside; from adjacent spaces within the building, provided the volume and infiltration rate is sufficient; or from the building air-conditioning system ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 409 Motion Picture Projection Rooms > 409.3 Projection Room and Equipment Ventilation > 409.3.1 Projection Room > 409.3.1.1 Supply Air
409.3 Special Detailed Requirements Based on Use and Occupancy, Projection Room and Equipment Ventilation
adjacent spaces within the building, provided the volume and infiltration rate is sufficient; or from the building air-conditioning system, provided ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 409 Motion Picture Projection Rooms > 409.3 Projection Room and Equipment Ventilation