// CODE SNIPPET
C402.4.1 Air Barriers
JUMP TO FULL CODE CHAPTER
A continuous air barrier shall be provided throughout the building thermal envelope. The air barriers shall be permitted to be located on the inside or outside of the building envelope, located within the assemblies composing the envelope, or any combination thereof. The air barrier shall comply with Sections C402.4.1.1 and C402.4.1.2.
Exception: Air barriers are not required in buildings located in Climate Zones 1, 2 and 3.
The continuous air barrier shall be constructed to comply with the following:
- The air barrier shall be continuous for all assemblies that are the thermal envelope of the building and across the joints and assemblies.
- Air barrier joints and seams shall be sealed, including sealing transitions in places and changes in materials. Air barrier penetrations shall be sealed in accordance with Section C402.4.2. The joints and seals shall be securely installed in or on the joint for its entire length so as not to dislodge, loosen or otherwise impair its ability to resist positive and negative pressure from wind, stack effect and mechanical ventilation.
- Recessed lighting fixtures shall comply with Section C402.4.8. Where similar objects are installed which penetrate the air barrier, provisions shall be made to maintain the integrity of the air barrier.
Exception:
Buildings that comply with Section C402.4.1.2.3 are not required to comply with Items 1 and 3.
A continuous air barrier for the opaque building envelope shall comply with Section C402.4.1.2.1, C402.4.1.2.2, or C402.4.1.2.3.
Materials with an air permeability no greater than 0.004 cfm/ft2 (0.02 L/s • m2) under a pressure differential of 0.3 inches water gauge (w.g.) (75 Pa) when tested in accordance with ASTM E 2178 shall comply with this section. Materials in Items 1 through 15 shall be deemed to comply with this section provided joints are sealed and materials are installed as air barriers in accordance with the manufacturer's instructions.
- Plywood with a thickness of not less than 3/8 inch (10 mm).
- Oriented strand board having a thickness of not less than 3/8 inch (10 mm).
- Extruded polystyrene insulation board having a thickness of not less than 1/2 inch (12 mm).
- Foil-back polyisocyanurate insulation board having a thickness of not less than 1/2 inch (12 mm).
- Closed cell spray foam a minimum density of 1.5 pcf (2.4 kg/m3) having a thickness of not less than 11/2 inches (36 mm).
- Open cell spray foam with a density between 0.4 and 1.5 pcf (0.6 and 2.4 kg/m3) and having a thickness of not less than 4.5 inches (113 mm).
- Exterior or interior gypsum board having a thickness of not less than 1/2 inch (12 mm).
- Cement board having a thickness of not less than 1/2 inch (12 mm).
- Built up roofing membrane.
- Modified bituminous roof membrane.
- Fully adhered single-ply roof membrane.
- A Portland cement/sand parge, or gypsum plaster having a thickness of not less than 5/8 inch (16 mm).
- Cast-in-place and precast concrete.
- Fully grouted concrete block masonry.
- Sheet steel or aluminum.
Assemblies of materials and components with an average air leakage not to exceed 0.04 cfm/ft2 (0.2 L/s • m2) under a pressure differential of 0.3 inches of water gauge (w.g.)(75 Pa) when tested in accordance with ASTM E 2357, ASTM E 1677 or ASTM E 283 shall comply with this section. Assemblies listed in Items 1 and 2 shall be deemed to comply provided joints are sealed and requirements of Section C402.4.1.1 are met.
- Concrete masonry walls coated with one application either of block filler and two applications of a paint or sealer coating;
- A Portland cement/sand parge, stucco or plaster minimum 1/2 inch (12 mm) in thickness.
The completed building shall be tested and the air leakage rate of the building envelope shall not exceed 0.40 cfm/ft2 at a pressure differential of 0.3 inches water gauge (2.0 L/s • m2 at 75 Pa) in accordance with ASTM E 779 or an equivalent method approved by the code official.
Related Code Sections
C402.4.1 [CE] Commercial Energy Efficiency, Air Barriers
A continuous air barrier shall be provided throughout the building thermal envelope. The air barriers shall be permitted to be located on the inside ...
Energy Conservation Code 2012 of Nevada > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.4 Air Leakage (Mandatory) > C402.4.1 Air Barriers
C402.5.1 [CE] Commercial Energy Efficiency, Air Barriers
A continuous air barrier shall be provided throughout the building thermal envelope. The air barriers shall be permitted to be located on the inside ...
Energy Conservation Code 2018 of Nevada > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.5 Air Leakage—Thermal Envelope (Mandatory) > C402.5.1 Air Barriers
5.4.3.1 Building Envelope, Continuous Air Barrier
The entire building envelope shall be designed and constructed with a continuous air barrier. Exceptions to 5.4.3.1 Semiheated spaces ...
Energy Standard for Buildings Except Low-Rise Residential Buildings 2016 of Nevada > 5 Building Envelope > 5.4 Mandatory Provisions > 5.4.3 Air Leakage > 5.4.3.1 Continuous Air Barrier
C402.4.1.2 [CE] Commercial Energy Efficiency, Air Barrier Compliance Options
A continuous air barrier for the opaque building envelope shall comply with Section C402.4.1.2.1, C402.4.1.2.2, or C402.4.1.2.3 ...
Energy Conservation Code 2012 of Nevada > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.4 Air Leakage (Mandatory) > C402.4.1 Air Barriers > C402.4.1.2 Air Barrier Compliance Options
C402.5.1.2 [CE] Commercial Energy Efficiency, Air Barrier Compliance Options
A continuous air barrier for the opaque building envelope shall comply with Section C402.5.1.2.1 or C402.5.1.2.2 ...
Energy Conservation Code 2018 of Nevada > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.5 Air Leakage—Thermal Envelope (Mandatory) > C402.5.1 Air Barriers > C402.5.1.2 Air Barrier Compliance Options