C402.4.1.1 Air Barrier Construction
JUMP TO FULL CODE CHAPTER
The continuous air barrier shall be constructed to comply with the following:
- The air barrier shall be continuous for all assemblies that are the thermal envelope of the building and across the joints and assemblies.
- Air barrier joints and seams shall be sealed, including sealing transitions in places and changes in materials. Air barrier penetrations shall be sealed in accordance with Section C402.4.2. The joints and seals shall be securely installed in or on the joint for its entire length so as not to dislodge, loosen or otherwise impair its ability to resist positive and negative pressure from wind, stack effect and mechanical ventilation.
- Recessed lighting fixtures shall comply with Section C402.4.8. Where similar objects are installed which penetrate the air barrier, provisions shall be made to maintain the integrity of the air barrier.
Exception:
Buildings that comply with Section C402.4.1.2.3 are not required to comply with Items 1 and 3.
Related Code Sections
C402.4.1.1 [CE] Commercial Energy Efficiency, Air Barrier Construction
The continuous air barrier shall be constructed to comply with the following:
The air barrier shall be continuous for all assemblies ...
Energy Conservation Code 2012 of Nevada > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.4 Air Leakage (Mandatory) > C402.4.1 Air Barriers > C402.4.1.1 Air Barrier Construction
C402.5.1.1 [CE] Commercial Energy Efficiency, Air Barrier Construction
The continuous air barrier shall be constructed to comply with the following: The air barrier shall be continuous for all assemblies ...
Energy Conservation Code 2018 of Nevada > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.5 Air Leakage—Thermal Envelope (Mandatory) > C402.5.1 Air Barriers > C402.5.1.1 Air Barrier Construction
5.9.2.2 Building Envelope, Air Leakage Verification
components and assemblies shall be conducted during construction while the air barrier is still accessible for inspection and repair to verify ...
Energy Standard for Buildings Except Low-Rise Residential Buildings 2016 of Nevada > 5 Building Envelope > 5.9 Inspection and Verification > 5.9.2 Verification > 5.9.2.2 Air Leakage Verification
5.4.3.1.1 Building Envelope, Continuous Air Barrier Design
The continuous air barrier shall be designed and noted in the following manner: All air barrier components of each building envelope assembly ...
Energy Standard for Buildings Except Low-Rise Residential Buildings 2016 of Nevada > 5 Building Envelope > 5.4 Mandatory Provisions > 5.4.3 Air Leakage > 5.4.3.1 Continuous Air Barrier > 5.4.3.1.1 Continuous Air Barrier Design
5.4.3.1 Building Envelope, Continuous Air Barrier
The entire building envelope shall be designed and constructed with a continuous air barrier. Exceptions to 5.4.3.1 Semiheated spaces ...
Energy Standard for Buildings Except Low-Rise Residential Buildings 2016 of Nevada > 5 Building Envelope > 5.4 Mandatory Provisions > 5.4.3 Air Leakage > 5.4.3.1 Continuous Air Barrier