// CODE SNIPPET
908.7.1.1 Affected Dwelling Units
JUMP TO FULL CODE CHAPTER
Carbon monoxide alarms or detectors shall be required within the following dwelling units:
- Units on the same story where carbon monoxide- producing equipment or enclosed parking is located.
- Units on the stories immediately above and below the floor where carbon monoxide-producing equipment or enclosed parking is located.
- Units in a building containing a carbon monoxide-producing furnace, boiler, or water heater as part of a central system.
- Units in a building served by a carbon monoxide- producing furnace, boiler, or water heater as part of a central system that is located in an adjoining or attached building.
Carbon monoxide alarms or detectors shall be located within dwelling units as follows:
- Outside of any room used for sleeping purposes, within 15 feet (4572 mm) of the entrance to such room.
- In any room used for sleeping purposes.
- On any story within a dwelling unit, including below-grade stories and penthouses of any area, but not including crawl spaces and uninhabitable attics.
Carbon monoxide alarms or detectors shall comply with the power source, interconnection and acceptance testing requirements as required for smoke alarms in accordance with Sections 907.2.11.2 through 907.2.11.3 and Section 907.7.1.
*Section 908.7.1.1.2 was amended by Local Law 157 of 2016.
*Section 908.7.1.1.2 was amended by Local Law 157 of 2016.
Means of exhausting carbon monoxide from garages shall be provided when a carbon monoxide alarm or detector is activated in a Group R-3 occupancy, provided such garage is attached within the Group R-3 occupancy. Such exhaust system shall be arranged to operate automatically upon detection of a concentration of carbon monoxide of 35 parts per million (ppm) or greater by approved automatic detection device. The system shall be capable of producing an exhaust rate of 1.5 cfm per square foot of floor area of the garage. Removal of sensor, interruption of power or cut wires shall cause the relay circuit to open and start fan. The relay contact shall close and the fan may shut off when the carbon monoxide level is below 35 ppm. Carbon monoxide exhausting means shall be connected to a separate circuit and provided with a lock and identified at the power source. Such circuit shall not be connected to a power source through an arc-fault or Ground Fault Circuit Interrupter (GFCI) devices. Additionally, when the carbon monoxide exhausting means is connected to the plug-in-type overcurrent protection device, such device shall be secured in place by an additional fastener.
Related Code Sections
908.7.1.1 Fire Protection Systems, Affected Dwelling Units
Carbon monoxide alarms or detectors shall be required within the following dwelling units: Units on the same story where carbon monoxide- producing ...
NYC Building Code 2014 > 9 Fire Protection Systems > 908 Emergency Alarm Systems > 908.7 Carbon Monoxide Alarms and Detectors > 908.7.1 Group I-1 and R Occupancies > 908.7.1.1 Affected Dwelling Units
908.7.1.1 Fire Protection Systems, Affected Dwelling Units
Carbon monoxide alarms or detectors shall be required within the following dwelling units: 1. Units on the same story where carbon ...
NYC Building Code 2008 > 9 Fire Protection Systems > 908 Emergency Alarm Systems > 908.7 Carbon Monoxide Alarms and Detectors > 908.7.1 Group I-1 and R Occupancies > 908.7.1.1 Affected Dwelling Units
908.7.1 Fire Protection Systems, Group I-1 and R Occupancies
notification appliances shall be installed in affected dwelling units as per Section 908.7.1.1 and shall be annunciated by dwelling unit at a constantly ...
NYC Building Code 2008 > 9 Fire Protection Systems > 908 Emergency Alarm Systems > 908.7 Carbon Monoxide Alarms and Detectors > 908.7.1 Group I-1 and R Occupancies
908.7 Fire Protection Systems, Carbon Monoxide Alarms and Detectors
: 1. Group R-1. Carbon monoxide detectors and audible notification appliances shall be installed in affected dwelling units as per Section ...
NYC Building Code 2008 > 9 Fire Protection Systems > 908 Emergency Alarm Systems > 908.7 Carbon Monoxide Alarms and Detectors
908.7.1 Fire Protection Systems, Group I-1 and R Occupancies
in affected dwelling units as per Section 908.7.1.1 and shall be annunciated by dwelling unit at a constantly attended location from which the fire alarm ...
NYC Building Code 2014 > 9 Fire Protection Systems > 908 Emergency Alarm Systems > 908.7 Carbon Monoxide Alarms and Detectors > 908.7.1 Group I-1 and R Occupancies