5106.3 Aerosol Product Display and Normal Merchandising Exceeding 8 Feet in Height

Jump To Full Code Chapter
Aerosol product display and merchandising exceeding 8 feet (2438 mm) in height shall be in accordance with Sections 5106.3.1 through 5106.3.3.
5106.3.1 Maximum Quantities in Retail Display Areas
Aerosol products in retail display areas shall not exceed quantities needed for display and normal merchandising and shall not exceed the quantities in Table 5106.2.1, with fire protection in accordance with Section 5106.3.2.
5106.3.2 Automatic Sprinkler Protection
Aerosol product and plastic aerosol 3 product display and merchandising areas shall be protected by an automatic sprinkler system based on the requirements set forth in Tables 6.4.2.7(a) through 6.4.2.7(1) of NFPA 30B and the following:
  1. Protection shall be based on the highest level of aerosol product in the array and the packaging method of the storage located more than 6 feet (1829 mm) above the finished floor.
  2. Where using the cartoned aerosol products tables of NFPA 30B, uncartoned or display-cut Level 2 and 3 aerosol products and plastic aerosol 3 products shall not be permitted more than 6 feet (1829 mm) above the finished floor.
  3. The design area for Level 2 and 3 aerosol products and plastic aerosol 3 products shall extend not less than 20 feet (6096 mm) beyond the Level 2 and 3 aerosol product and plastic aerosol 3 product display and merchandising areas.
  4. Where ordinary and high-temperature ceiling sprinkler systems are adjacent to each other, noncombustible draft curtains shall be installed at the interface.
5106.3.3 Separation of Level 2 and 3 Aerosol Product and Plastic Aerosol 3 Product Areas
Separation of Level 2 and 3 aerosol product areas or plastic aerosol 3 product areas shall comply with the following:
  1. Level 2 and 3 aerosol product or plastic aerosol 3 product display and merchandising areas shall be separated from each other by not less than 25 feet (7620 mm). See Table 5106.2.1.
  2. Level 2 and 3 aerosol product or plastic aerosol 3 product display and merchandising areas shall be separated from flammable and combustible liquids storage and display areas by one or a combination of the following:
    2.1. Segregating areas from each other by horizontal distance of not less than 25 feet (7620 mm).
    2.2. Isolating areas from each other by a noncombustible partition extending not less than 18 inches (457 mm) above the merchandise.
    2.3. In accordance with Section 5106.5.
  3. Where Item 2.2 is used to separate Level 2 or 3 aerosol products or plastic aerosol 3 products from flammable or combustible liquids, and the aerosol products are located within 25 feet (7620 mm) of flammable or combustible liquids, the area below the noncombustible partition shall be liquid tight at the floor to prevent spilled liquids from flowing beneath the aerosol products.

Related Code Sections

Section 5106 Aerosols, Retail Display
Aerosol product display and merchandising exceeding 8 feet (2438 mm) in height ...
5106.2 Aerosols, Aerosol Display and Normal Merchandising Not Exceeding 8 Feet in Height
Aerosol display and normal merchandising not exceeding 8 feet (2438 mm) in height shall be in accordance with Sections 5106.2.1 through 5106.2.5 ...
5106.3 Aerosols, Aerosol Product Display and Normal Merchandising Exceeding 8 Feet High
Aerosol product display and merchandising exceeding 8 feet (2438 mm) in height shall be in accordance with Sections 5106.3.1 through 5106.3.3 ...
5106.2.3 Aerosols, Display of Aerosol Products
is on shelves, the height of such storage or retail display to the top of aerosol products shall not exceed 8 feet (2438 mm) ...