Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

5106.2 Aerosol Display and Normal Merchandising Not Exceeding 8 Feet (2438 MM) High

Fire Code 2015 of Alabama > 51 Aerosols > 5106 Retail Display > 5106.2 Aerosol Display and Normal Merchandising Not Exceeding 8 Feet (2438 MM) High
JUMP TO FULL CODE CHAPTER
Aerosol display and normal merchandising not exceeding 8 feet (2438 mm) in height shall be in accordance with Sections 5106.2.1 through 5106.2.4.

5106.2.1 Maximum Quantities in Retail Display Areas

Aerosol products in retail display areas shall not exceed quantities needed for display and normal merchandising and shall not exceed the quantities in Table 5106.2.1.

TABLE 5106.2.1
MAXIMUM QUANTITIES OF LEVEL 2 AND 3 AEROSOL PRODUCTS IN RETAIL DISPLAY AREAS
MAXIMUM NET WEIGHT PER FLOOR (pounds)b
Floor Unprotecteda Protected in
accordance with
Section 5106.2a, c
Protected in
accordance with
Section 5106.3c
Basement Not allowed 500 500
Ground 2,500 10,000 10,000
Upper 500 2,000 Not allowed

For SI: 1 pound = 0.454 kg, 1 square foot = 0.0929 m2.
  1. The total quantity shall not exceed 1,000 pounds net weight in any one 100-square-foot retail display area.
  2. Per 25,000-square-foot retail display area.
  3. Minimum Ordinary Hazard Group 2 wet-pipe automatic sprinkler system throughout the retail sales occupancy.

5106.2.2 Display of Containers

Level 2 and 3 aerosol containers shall not be stacked more than 6 feet (1829 mm) high from the base of the aerosol array to the top of the aerosol array unless the containers are placed on fixed shelving or otherwise secured in an approved manner. Where storage or retail display is on shelves, the height of such storage or retail display to the top of aerosol containers shall not exceed 8 feet (2438 mm).

5106.2.3 Combustible Cartons

Aerosol products located in retail display areas shall be removed from combustible cartons.

Exceptions:
  1. Display areas that use a portion of combustible cartons that consist of only the bottom panel and not more than 2 inches (51 mm) of the side panel are allowed.
  2. When the display area is protected in accordance with Tables 6.3.2.7(a) through 6.3.2.7(l) of NFPA 30B, storage of aerosol products in combustible cartons is allowed.

5106.2.4 Retail Display Automatic Sprinkler System

ILLUSTRATION
Where an automatic sprinkler system is required for the protected retail display of aerosol products, the wet-pipe automatic sprinkler system shall be in accordance with Section 903.3.1.1. The minimum system design shall be for an Ordinary Hazard Group 2 occupancy. The system shall be provided throughout the retail display area.

Related Code Sections


2806.2.2 Aerosols, Display of Containers
, the height of such storage or retail display to the top of aerosol containers shall not exceed 8 feet (2438 mm) ...
Fire Code 2009 of Alabama > 28 Aerosols > 2806 Retail Display > 2806.2 Aerosol Display and Normal Merchandising Not Exceeding 8 Feet (2438 MM) High > 2806.2.2 Display of Containers
5106.2.2 Aerosols, Display of Containers
, the height of such storage or retail display to the top of aerosol containers shall not exceed 8 feet (2438 mm) ...
Fire Code 2015 of Alabama > 51 Aerosols > 5106 Retail Display > 5106.2 Aerosol Display and Normal Merchandising Not Exceeding 8 Feet (2438 MM) High > 5106.2.2 Display of Containers
5106.2.4 Aerosols, Retail Display Automatic Sprinkler System
Where an automatic sprinkler system is required for the protected retail display of aerosol products, the wet-pipe automatic sprinkler system ...
Fire Code 2015 of Alabama > 51 Aerosols > 5106 Retail Display > 5106.2 Aerosol Display and Normal Merchandising Not Exceeding 8 Feet (2438 MM) High > 5106.2.4 Retail Display Automatic Sprinkler System
2806.2 Aerosols, Aerosol Display and Normal Merchandising Not Exceeding 8 Feet (2438 MM) High
Aerosol display and normal merchandising not exceeding 8 feet (2438 mm) in height shall be in accordance with Sections 2806.2.1 through 2806.2.4 ...
Fire Code 2009 of Alabama > 28 Aerosols > 2806 Retail Display > 2806.2 Aerosol Display and Normal Merchandising Not Exceeding 8 Feet (2438 MM) High
5106.2 Aerosols, Aerosol Display and Normal Merchandising Not Exceeding 8 Feet (2438 MM) High
Aerosol display and normal merchandising not exceeding 8 feet (2438 mm) in height shall be in accordance with Sections 5106.2.1 through 5106.2.4 ...
Fire Code 2015 of Alabama > 51 Aerosols > 5106 Retail Display > 5106.2 Aerosol Display and Normal Merchandising Not Exceeding 8 Feet (2438 MM) High
Help Contact Us Privacy Terms
Code Compare
Code Compare
Highlight differences between any two building codes.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING