1224.4.4.2 Administrative Center(s) or Nurse Station(s)
JUMP TO FULL CODE CHAPTER
This area shall have space for counters and storage and at least one hand-washing station shall be located in, adjacent to, or directly accessible to the administrative center or nurse station. It may be combined with or include centers for reception, charting and communication.
Related Code Sections
1224.4.4.2 Interior Environment, Administrative Center(s) or Nurse Station(s)
to the administrative center or nurse station. It may be combined with or include centers for reception, charting and communication ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.4 General Construction > 1224.4.4 Support Areas for Patient Care > 1224.4.4.2 Administrative Center(s) or Nurse Station(s)
1226.4.13.1 Interior Environment, Administrative Center(s) or Nurse Station(s)
of handwashing station). It may be combined with or include centers for reception, charting and communication ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1226 [OSHPD 3] Clinics > 1226.4 General Construction > 1226.4.13 Support Areas for Examination and Treatment Rooms > 1226.4.13.1 Administrative Center(s) or Nurse Station(s)
1228.14.2.1 Interior Environment, Administrative Center(s) or Nurse Station(s)
Refer to
Section 1228.4.22 for the definition of handwashing
station. Handwashing stations in high- or mediumpatient ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1228 Acute Psychiatric Hospitals > 1228.14 Psychiatric Nursing Service Space > 1228.14.2 Service Areas > 1228.14.2.1 Administrative Center(s) or Nurse Station(s)
1228.14.2.1 Interior Environment, Administrative Center(s) or Nurse Station(s)
Refer to
Section 1228.4.22 for the definition of handwashing
station. Handwashing stations in high- or mediumpatient-
risk ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1228 [OSHPD 5] Acute Psychiatric Hospitals > 1228.14 Psychiatric Nursing Service Space > 1228.14.2 Service Areas > 1228.14.2.1 Administrative Center(s) or Nurse Station(s)
1228.4.4.2 Interior Environment, Administrative Center(s) or Nurse Station(s)
Refer to Section 1224.4.4.2 ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1228 [OSHPD 5] Acute Psychiatric Hospitals > 1228.4 General Construction > 1228.4.4 Support Areas for Patients > 1228.4.4.2 Administrative Center(s) or Nurse Station(s)