R703.12 Adhered Masonry Veneer Installation
JUMP TO FULL CODE CHAPTER
Adhered masonry veneer shall comply with the requirements of Section R703.7.3 and the requirements in Sections 12.1 and 12.3 of TMS 402. Adhered masonry veneer shall be installed in accordance with Section R703.7.1, Article 3.3C of TMS 602 or the manufacturer's instructions.
On exterior stud walls, adhered masonry veneer shall be installed:
- Minimum of 4 inches (102 mm) above the earth;
- Minimum of 2 inches (51 mm) above paved areas; or
- Minimum of 1/2 inch (12.7 mm) above exterior walking surfaces that are supported by the same foundation that supports the exterior wall.
A corrosion-resistant screed or flashing of a minimum 0.019-inch (0.48 mm) or 26-gage galvanized or plastic with a minimum vertical attachment flange of 31/2 inches (89 mm) shall be installed to extend a minimum of 1 inch (25 mm) below the foundation plate line on exterior stud walls in accordance with Section R703.4.
A water-resistive barrier shall be installed as required by Section R703.2 and shall comply with the requirements of Section R703.7.3. The water-resistive barrier shall lap over the exterior of the attachment flange of the screed or flashing provided in accordance with Section R703.12.2.
Related Code Sections
R703.12 Wall Covering, Adhered Masonry Veneer Installation
On exterior stud walls, adhered masonry veneer shall be installed ...
Residential Code 2018 of Kansas > 7 Wall Covering > R703 Exterior Covering > R703.12 Adhered Masonry Veneer Installation
1404.10.1.4 Exterior Walls, Adhered Masonry Veneer Installed With Lath and Mortar
Exterior adhered masonry veneer installed with lath and mortar shall comply with the following ...
Building Code 2018 of Kansas > 14 Exterior Walls > 1404 Installation of Wall Coverings > 1404.10 Adhered Masonry Veneer > 1404.10.1 Exterior Adhered Masonry Veneer > 1404.10.1.4 Adhered Masonry Veneer Installed With Lath and Mortar
R703.12.3 Wall Covering, Water-Resistive Barrier
A water-resistive barrier shall be installed as required by Section R703.2 and shall comply with the requirements of Section R703.7.3. The water ...
Residential Code 2018 of Kansas > 7 Wall Covering > R703 Exterior Covering > R703.12 Adhered Masonry Veneer Installation > R703.12.3 Water-Resistive Barrier
R606.14.2 Wall Construction, Adhered Veneer
Adhered masonry veneer shall be installed in accordance with the requirements of Section R703.12 ...
Residential Code 2018 of Kansas > 6 Wall Construction > R606 General Masonry Construction > R606.14 Anchored and Adhered Masonry Veneer > R606.14.2 Adhered Veneer
R606.14 Wall Construction, Anchored and Adhered Masonry Veneer
Adhered masonry veneer shall be installed in accordance ...
Residential Code 2018 of Kansas > 6 Wall Construction > R606 General Masonry Construction > R606.14 Anchored and Adhered Masonry Veneer