404.5 Adequate Water Supply
JUMP TO FULL CODE CHAPTER
Adequate water supply shall be determined for purposes of initial attack and flame front control as follows:
- One- and two-family dwellings. The required water supply for one- and two-family dwellings having a fire area that does not exceed 3,600 square feet (334 m2) shall be 1,000 gallons per minute (63.1 L/s) for a minimum duration of 30 minutes. The required water supply for one- and two-family dwellings having a fire area in excess of 3,600 square feet (334 m2) shall be 1,500 gallons per minute (95 L/s) for a minimum duration of 30 minutes.
Exception: A reduction in required flow rate of 50 percent, as approved by the code official, is allowed when the building is provided with an approved automatic sprinkler system.
- Buildings other than one- and two-family dwellings. The water supply required for buildings other than one- and two-family dwellings shall be as approved by the code official but shall not be less than 1,500 gallons per minute (95 L/s) for a duration of two hours.
Exception: A reduction in required flow rate of up to 75 percent, as approved by the code official, is allowed when the building is provided with an approved automatic sprinkler system. The resulting water supply shall not be less than 1,500 gallons per minute (94.6 L/s).
Related Code Sections
404.5 Wildland-Urban Interface Area Requirements, Adequate Water Supply
Adequate water supply shall be determined for purposes of initial attack and flame front control as follows:
One- and two-family dwellings. The ...
Wildland-Urban Interface Code 2009 of Pennsylvania > 4 Wildland-Urban Interface Area Requirements > 404 Water Supply > 404.5 Adequate Water Supply
404.5 Wildland-Urban Interface Area Requirements, Adequate Water Supply
Adequate water supply shall be determined for purposes of initial attack and flame front control as follows:
One- and two-family dwellings. The ...
Wildland-Urban Interface Code 2015 of Pennsylvania > 4 Wildland-Urban Interface Area Requirements > 404 Water Supply > 404.5 Adequate Water Supply
404.10.3 Wildland-Urban Interface Area Requirements, Standby Power
Stationary water supply facilities within the wildland-urban interface area dependent on electrical power to meet adequate water supply demands ...
Wildland-Urban Interface Code 2009 of Pennsylvania > 4 Wildland-Urban Interface Area Requirements > 404 Water Supply > 404.10 Reliability > 404.10.3 Standby Power
Section 404 Wildland-Urban Interface Area Requirements, Water Supply
with Section 402.1.2, an approved water source shall have an adequate water supply for the use of the fire protection service to protect buildings ...
Wildland-Urban Interface Code 2015 of Pennsylvania > 4 Wildland-Urban Interface Area Requirements > 404 Water Supply
404.10 Wildland-Urban Interface Area Requirements, Reliability
dependent on electrical power to meet adequate water supply demands shall provide standby power systems in accordance with Chapter 27 ...
Wildland-Urban Interface Code 2009 of Pennsylvania > 4 Wildland-Urban Interface Area Requirements > 404 Water Supply > 404.10 Reliability