On existing stacks in buildings where the center of a water closet outlet is more than 4 feet but not more than 8 feet from the center of a vented soil pipe, an additional 1-1/2 inch vent will be permitted if the vent is not longer than 30 feet, provided the conditions are the same as in Section P-1105.1.1.

Figure P-1105.1.2

WATER CLOSET IN EXCESS OF 48" OF EXISTING STACK
Upcodes Diagrams