// CODE SNIPPET
5704.2.9.7 Additional Requirements for Protected Above-Ground Tanks
Go To Full Code Chapter
In addition to the requirements of this chapter for above-ground tanks, the installation of protected above-ground tanks shall be in accordance with Sections 5704.2.9.7.1 through 5704.2.9.7.9.
5704.2.9.7.1 Tank Construction
The construction of a protected above-ground tank and its primary tank shall be in accordance with Section 5704.2.7.
5704.2.9.7.2 Normal and Emergency Venting
Normal and emergency venting for protected above-ground tanks shall be provided in accordance with Sections 5704.2.7.3 and 5704.2.7.4. The vent capacity reduction factor shall not be allowed.
5704.2.9.7.3 Secondary Containment
Protected above-ground tanks shall be provided with secondary containment, drainage control or diking in accordance with Section 5004.2. A means shall be provided to establish the integrity of the secondary containment in accordance with NFPA 30.
5704.2.9.7.4 Vehicle Impact Protection
Where protected above-ground tanks, piping, electrical conduit or dispensers are subject to vehicular impact, they shall be protected therefrom, either by having the impact protection incorporated into the system design in compliance with the impact test protocol of UL 2085, or by meeting the provisions of Section 312, or where necessary, a combination of both. Where guard posts or other approved barriers are provided, they shall be independent of each above-ground tank.
5704.2.9.7.5 Overfill Prevention
Protected above-ground tanks shall not be filled in excess of 95 percent of their capacity. An overfill prevention system shall be provided for each tank. During tank-filling operations, the system shall comply with one of the following:
- The overfill prevention system shall include the following:
- An independent means of notifying the person filling the tank that the fluid level has reached 90 percent of tank capacity by providing an audible or visual alarm signal, providing a tank level gauge marked at 90 percent of tank capacity, or other approved means.
- Automatic shut off of the flow of fuel to the tank when the quantity of liquid in the tank reaches 95 percent of tank capacity. For rigid hose fuel-delivery systems, an approved means shall be provided to empty the fill hose into the tank after the automatic shutoff device is activated.
- The system shall reduce the flow rate to not more than 15 gallons per minute (0.95 L/s) so that at the reduced flow rate, the tank will not overfill for 30 minutes, and automatically shut off flow into the tank so that none of the fittings on the top of the tank are exposed to product because of overfilling.
5704.2.9.7.5.1 Information Signs
A permanent sign shall be provided at the fill point for the tank, documenting the filling procedure and the tank calibration chart.
Exception: Where climatic conditions are such that the sign may be obscured by ice or snow, or weathered beyond readability or otherwise impaired, said procedures and chart shall be located in the office window, lock box or other area available to the person filling the tank.
5704.2.9.7.5.2 Determination of Available Tank Capacity
The filling procedure shall require the person filling the tank to determine the gallonage (literage) required to fill it to 90 percent of capacity before commencing the fill operation.
5704.2.9.7.6 Fill Pipe Connections
The fill pipe shall be provided with a means for making a direct connection to the tank vehicle's fuel delivery hose so that the delivery of fuel is not exposed to the open air during the filling operation. Where any portion of the fill pipe exterior to the tank extends below the level of the top of the tank, a check valve shall be installed in the fill pipe not more than 12 inches (305 mm) from the fill hose connection.
5704.2.9.7.7 Spill Containers
A spill container having a capacity of not less than 5 gallons (19 L) shall be provided for each fill connection. For tanks with a top fill connection, spill containers shall be noncombustible and shall be fixed to the tank and equipped with a manual drain valve that drains into the primary tank. For tanks with a remote fill connection, a portable spill container shall be allowed.
5704.2.9.7.8 Tank Openings
Related Code Sections
5704.2.9.7 Flammable and Combustible Liquids, Additional Requirements for Protected Above-Ground Tanks
In addition to the requirements of this chapter for above-ground tanks, the installation of protected above-ground tanks shall be in accordance ...
5704.2.9.7 Flammable and Combustible Liquids, Additional Requirements for Protected Above-Ground Tanks
In addition to the requirements of this chapter for above-ground tanks, the installation of protected above-ground tanks shall be in accordance ...
5704.2.9.7.4 Flammable and Combustible Liquids, Vehicle Impact Protection
Where protected above-ground tanks, piping, electrical conduit or dispensers are subject to vehicular impact, they shall be protected therefrom ...
5704.2.9.7.2 Flammable and Combustible Liquids, Normal and Emergency Venting
Normal and emergency venting for protected above-ground tanks shall be provided in accordance with Sections 5704.2.7.3 and 5704.2.7.4. The vent ...
5704.2.9.7.2 Flammable and Combustible Liquids, Normal and Emergency Venting
Normal and emergency venting for protected above-ground tanks shall be provided in accordance with Sections 5704.2.7.3 and 5704.2.7.4. The vent ...