Where deep foundations are used, the geotechnical investigation and report provisions of Section 1803 shall be expanded to include, but not be limited to, consideration of the following:
  1. Recommended deep foundation types and their capacities.
  2. Designation of bearing stratum or strata.
  3. Suitable center-to-center spacing of deep foundation elements.
  4. Reductions for group action, where necessary.
  5. Load test requirements.
  6. Durability of pile materials.
  7. Installation procedures.
  8. Protection of adjacent structures due to installation.
  9. Field inspection and reporting procedures (to include procedures for verification of the installed bearing capacity where required).
Upcodes Diagrams

Related Code Sections

1818.5 Soils and Foundations, Geotechnical Peer Review Report
addition, the report shall also include the following: The codes and standards used in the geotechnical design of the project. The basis ...
1802.4 Soils and Foundations, Investigation
An engineer shall scope and supervise the geotechnical investigation. The geotechnical investigation shall be sufficient for evaluating soil and rock ...