2107.5 ACI 530/ASCE 5/TMS 402, Section 2.1.10.7.1.1, Lap Splices
Go To Full Code Chapter
Modify Section 2.1.10.7.1.1 as follows:
2.1.10.7.1.1 The minimum length of lap splices for reinforcing bars in tension or compression, ld, shall be
For SI: ld = 0.29dbfs
but not less than 12 inches (305 mm). In no case shall the length of the lapped splice be less than 40 bar diameters.
where:
db = Diameter of reinforcement, inches (mm).
fs = Computed stress in reinforcement due to design loads, psi (MPa).
In regions of moment where the design tensile stresses in the reinforcement are greater than 80 percent of the allowable steel tension stress, Fs, the lap length of splices shall be increased not less than 50 percent of the minimum required length. Other equivalent means of stress transfer to accomplish the same 50 percent increase shall be permitted.
Where epoxy coated bars are used, lap length shall be increased by 50 percent.
ld = 0.002dbfs
(Equation 21-2)
For SI: ld = 0.29dbfs
but not less than 12 inches (305 mm). In no case shall the length of the lapped splice be less than 40 bar diameters.
where:
db = Diameter of reinforcement, inches (mm).
fs = Computed stress in reinforcement due to design loads, psi (MPa).
In regions of moment where the design tensile stresses in the reinforcement are greater than 80 percent of the allowable steel tension stress, Fs, the lap length of splices shall be increased not less than 50 percent of the minimum required length. Other equivalent means of stress transfer to accomplish the same 50 percent increase shall be permitted.
Where epoxy coated bars are used, lap length shall be increased by 50 percent.
Related Code Sections
2107.5 Masonry, ACI 530/ASCE 5/TMS 402, Section 2.1.10.7.1.1, Lap Splices
Modify Section 2.1.10.7.1.1 as follows:
2.1.10.7.1.1 The minimum length of lap splices for reinforcing bars in tension or compression, ld ...
2107.2.1 Masonry, Lap Splices
The minimum length of lap splices for reinforcing bars in tension or compression, ld, shall be (Equation 21-1) For SI: ld = 0.002dbfs ...
2106.1.1 Masonry, Basic Seismic-Force-Resisting System
with the requirements of Section 1.14.2.2.4 of ACI 530/ASCE 5/TMS 402 and shall be designed by Chapter 4, Section 4.4.3, of ACI 530/ASCE 5/TMS 402 for flexural ...
2109.1 Masonry, General
Empirically designed masonry shall conform to the requirements of Appendix A of TMS 402/ACI 530/ASCE 5, except where otherwise noted in this section ...
2101.2 Masonry, Design Methods
Prestressed masonry shall be designed in accordance with Chapters 1 and 4 of ACI 530/ASCE 5/TMS 402 and Section 2106. Special inspection during construction ...