2107.2.3 ACI 530/ASCE 5/TMS 402, Section 2.1.10.6.1.1, Lap Splices
JUMP TO FULL CODE CHAPTER
(Equation 21-2)
For SI: lld = 1.95d2bfyλ / K√f'm
where:
The minimum length of lap splices for reinforcing bars in tension or compression, lld, shall be calculated by Equation 21-2, but shall not be less than 15 inches (381 mm).
For SI: lld = 1.95d2bfyλ / K√f'm
where:
db | = | Diameter of reinforcement, inches (mm). |
---|---|---|
ƒy | = | Specified yield stress of the reinforcement or the anchor bolt, psi (mPa). |
ƒ'm | = | Specified compressive strength of masonry at age of 28 days, psi (mPa). |
lld | = | Minimum lap splice length, inches (mm). |
K | = | The lesser of the masonry cover, clear spacing between adjacent reinforcement or five times db, inches (mm). |
γ | = | 1.0 for No. 3 through No. 5 reinforcing bars. 1.4 for No.6 and No.7 reinforcing bars. 1.5 for No.8 through No. 9 reinforcing bars. |
Related Code Sections
2107.2.3 Masonry, ACI 530/ASCE 5/TMS 402, Section 2.1.10.6.1.1, Lap Splices
The minimum length of lap splices for reinforcing bars in tension or compression, l ld , shall be calculated by Equation 21-2, but shall ...
NYC Building Code 2008 > 21 Masonry > 2107 Working Stress Design > 2107.2 Modifications to ACI 530/ASCE 5/TMS 402 > 2107.2.3 ACI 530/ASCE 5/TMS 402, Section 2.1.10.6.1.1, Lap Splices
2106.1 Masonry, Seismic Design Requirements for Masonry
Masonry structures and components shall comply with the requirements in Section 1.13.2.2 of ACI 530/ASCE 5/TMS 402 and Section 1.13.3, 1.13.4, 1.13.5 ...
NYC Building Code 2008 > 21 Masonry > 2106 Seismic Design > 2106.1 Seismic Design Requirements for Masonry
Section 2107 Masonry, Allowable Stress Design
Section 2.1.2.1 and 2.1.3.3 of TMS 402/ACI 530/ASCE 5. The text of TMS 402/ACI 530/ASCE 5 shall be modified by Sections 2107.2 through 2107.5 of this code ...
2108.1 Masonry, General
402. The minimum nominal thickness for hollow clay masonry in accordance with Section 3.2.5.5 of ACI 530/ASCE 5/TMS 402 shall be 4 inches (102 mm ...
1405.6 Exterior Walls, Anchored Masonry Veneer
of Section 6.2.2.10 of TMS 402/ACI 530/ASCE 5. Anchored masonry veneer located in Seismic Design Category D shall also conform to the requirements ...
NYC Building Code 2014 > 14 Exterior Walls > 1405 Installation of Wall Coverings > 1405.6 Anchored Masonry Veneer