5704.2.8.15 Accessway
JUMP TO FULL CODE CHAPTER
Vaults shall be provided with an approved personnel accessway with a minimum dimension of 30 inches (762 mm) and with a permanently affixed, nonferrous ladder. Accessways shall be designed to be nonsparking. Travel distance from any point inside a vault to an accessway shall not exceed 20 feet (6096 mm). At each entry point, a warning sign indicating the need for procedures for safe entry into confined spaces shall be posted. Entry points shall be secured against unauthorized entry and vandalism.
Related Code Sections
5303.16.13 Compressed Gases, Accessway
Vaults shall be provided with an approved personnel accessway with a minimum dimension of 30 inches (762 mm) and with a permanently affixed ...
California Fire Code 2019 > 53 Compressed Gases > 5303 General Requirements > 5303.16 Vaults > 5303.16.13 Accessway
5303.16.13 Compressed Gases, Accessway
Vaults shall be provided with an approved personnel accessway with a minimum dimension of 30 inches (762 mm) and with a permanently affixed ...
California Fire Code 2016 > 53 Compressed Gases > 5303 General Requirements > 5303.16 Vaults > 5303.16.13 Accessway
5704.2.8.15 Flammable and Combustible Liquids, Accessway
Vaults shall be provided with an approved personnel accessway with a minimum dimension of 30 inches (762 mm) and with a permanently affixed ...
California Fire Code 2019 > 57 Flammable and Combustible Liquids > 5704 Storage > 5704.2 Tank Storage > 5704.2.8 Vaults > 5704.2.8.15 Accessway
5704.2.8.15 Flammable and Combustible Liquids, Accessway
Vaults shall be provided with an approved personnel accessway with a minimum dimension of 30 inches (762 mm) and with a permanently affixed ...