5.508.2.2.2 Access Valves
JUMP TO FULL CODE CHAPTER
Only Schrader access valves with a brass or steel body are permitted for use.
For systems with a refrigerant charge of 5 pounds or more, valve caps shall be brass or steel and not plastic.
If designed for it, the cap shall have a neoprene O-ring in place.
Chain tethers to fit over the stem are required for valves designed to have seal caps.
Exception: Valves with seal caps that are not removed from the valve during stem operation.
Related Code Sections
5.508.2.2.2 Nonresidential Mandatory Measures, Access Valves
Only Schrader access valves with a brass or steel body are permitted for use ...
Los Angeles Green Building Code > 5 Nonresidential Mandatory Measures > 5.508 Outdoor Air Quality > 5.508.2 Supermarket Refrigerant Leak Reduction > 5.508.2.2 Valves > 5.508.2.2.2 Access Valves
5.508.2.2.2 Nonresidential Mandatory Measures, Access Valves
Only Schrader access valves with a brass or steel body are permitted for use ...
Los Angeles Green Building Code > 5 Nonresidential Mandatory Measures > 5.508 Outdoor Air Quality > 5.508.2 Supermarket Refrigerant Leak Reduction > 5.508.2.2 Valves > 5.508.2.2.2 Access Valves
5305.4 Compressed Gases, Valves
Valves utilized on compressed gas systems shall be suitable for the use intended and shall be accessible. Valve handles or operators for required ...
2017 LA City Fire Code > 53 Compressed Gases > 5305 Use and Handling of Compressed Gases > 5305.4 Valves
5.508.2.2.2.2.1 Nonresidential Mandatory Measures, Chain Tethers
Chain tethers to fit over the stem are required for valves designed to have seal caps. Exception: Valves with seal caps that are not removed from ...
Los Angeles Green Building Code > 5 Nonresidential Mandatory Measures > 5.508 Outdoor Air Quality > 5.508.2 Supermarket Refrigerant Leak Reduction > 5.508.2.2 Valves > 5.508.2.2.2 Access Valves > 5.508.2.2.2.2 Seal Caps > 5.508.2.2.2.2.1 Chain Tethers