Appliances shall be accessible for inspection, service, repair and replacement without disabling the function of a fire-resistance-rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space at least 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance.
306.1.1 Central Furnaces
Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76 mm) along the sides, back and top with a total width of the enclosing space being at least 12 inches (305 mm) wider than the furnace. Furnaces having a firebox open to the atmosphere shall have at least 6 inches (152 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7.
Exception: This section shall not apply to replacement appliances installed in existing compartments and alcoves where the working space clearances are in accordance with the equipment or appliance manufacturer's installation instructions.

Related Code Sections

306.1 General Regulations, Access for Maintenance and Replacement
Appliances shall be accessible for inspection, service, repair and replacement without disabling the function of a fire-resistance-rated assembly ...
306.1 General Regulations, Access for Maintenance and Replacement
Appliances shall be accessible for inspection, service, repair and replacement without disabling the function of a fire-resistance-rated assembly ...
M2301.2.1 Solar Systems, Access
Solar energy collectors, controls, dampers, fans, blowers and pumps shall be accessible for inspection, maintenance, repair and replacement ...
501.4 Water Heaters, Location
Water heaters and storage tanks shall be located and connected so as to provide access for observation, maintenance, servicing and replacement ...