Section P-606 Abandoned Piping
Go To Full Code Chapter
P-606.1 Abandoned Drainage
Abandoned laterals shall have the house trap removed, and the pipe shall be
hermetically sealed by a cap or plug at the curb line. Abandoned drainage piping within the building shall be
hermetically sealed by a cap or plug.
P-606.2 Abandoned Water Piping
Abandoned water service shall be capped or plugged at the curb or shall have the
ferrule removed. Abandoned water piping within the building shall be capped or plugged with a fitting.
P-606.3 Permit
A plumbing permit is required for abandonment, and work shall be performed by a Registered Master
Plumber.
Related Code Sections
Section P-606 Pipe Supports, Abandoned Piping
Abandoned laterals shall have the house trap removed, and the pipe shall be
hermetically sealed by a cap or plug at the curb line. Abandoned drainage ...
P-615.3 Water Supply and Distribution, Abandoned Water Supply Pipe
Abandoned water
supply piping or water supply piping intended to serve future
fixtures within a building or structure shall be capped or
plugged ...
Section P-615 Water Supply and Distribution, Abandoned Water Supply System and Components
for a
discontinuance permit. Abandoned water service piping shall
be capped or plugged at the curb or shall have the ferrule
removed ...
3404.2.14.1 Flammable and Combustible Liquids, Removal
be removed from the ground.
Exception:
Piping is allowed to be abandoned in place where the fire code official determines that removal is not practical ...
5704.2.14.1 Flammable and Combustible Liquids, Removal
the ground. Exception: Piping is allowed to be abandoned in place where the fire code official determines that removal is not practical. Abandoned piping ...