G104.5.1 A-Zones
JUMP TO FULL CODE CHAPTER
For construction in A-Zones, the permit application shall include the following certifications, as applicable:
- Wet floodproofing certification. For wet floodproofed enclosures below the design flood elevation, construction documents shall include a certification by the applicant that the design provides for the automatic entry and exit of floodwaters for equalization of hydrostatic flood forces in accordance with Section 2.6.2, ASCE 24.
- Dry floodproofing certification for nonresidential buildings. For dry floodproofed buildings and structures that are nonresidential (for flood zone purposes), construction documents shall include a certification by the applicant that the dry floodproofing is designed in accordance with ASCE 24.
- Utility certifications. For all applications involving utility or mechanical work, including applications where such work is to be filed in a separate, related application, construction documents shall include a certification by the applicant that "all heating, ventilation, air conditioning, plumbing, electrical and other services facilities and equipment within the structure or site will be located or constructed so as to prevent water from entering or accumulating within the components during conditions of flooding in accordance with ASCE 24."
Related Code Sections
G104.5.1 Flood-Resistant Construction, A-Zones
For construction in A-Zones, the permit application shall include the following certifications, as applicable:
Wet floodproofing ...
NYC Building Code 2014 > G Flood-Resistant Construction > G104 Permits > G104.5 Certifications > G104.5.1 A-Zones
G104.5.1 Flood-Resistant Construction, A-Zones
For construction in A-Zones, the permit application shall include the following certifications, as applicable: Wet floodproofing certification ...
NYC Building Code 2008 > G Flood-Resistant Construction > G104 Permits > G104.5 Certifications > G104.5.1 A-Zones
G304.1 Flood-Resistant Construction, A-Zone Construction Standards
A-Zones, other than Coastal A-Zones. For buildings ...
NYC Building Code 2014 > G Flood-Resistant Construction > G304 Post-Firm Construction and Substantial Improvements > G304.1 A-Zone Construction Standards
G304.1 Flood-Resistant Construction, A-Zone Construction Standards
A-Zones, other than Coastal A-Zones. For buildings ...
NYC Building Code 2008 > G Flood-Resistant Construction > G304 Post-Firm Construction and Substantial Improvements > G304.1 A-Zone Construction Standards
G106.2 Flood-Resistant Construction, Spaces Subject to Flooding in A-Zones
The certificate of occupancy shall describe all wet floodproofed enclosed areas below the design flood elevation as "subject to flooding". Such wet ...
NYC Building Code 2008 > G Flood-Resistant Construction > G106 Certificates of Occupancy > G106.2 Spaces Subject to Flooding in A-Zones