A part-winding start induction or synchronous motor is one that is arranged for starting by first energizing part of its primary (armature) winding and, subsequently, energizing the remainder of this winding in one or more steps. A standard part-winding start induction motor is arranged so that one-half of its primary winding can be energized initially, and, subsequently, the remaining half can be energized, both halves then carrying equal current.
Go To Full Code Chapter

Related Code Sections

(D) Equipment for General Use, Part-Winding Motor
For a part-winding connected motor, the ampacity of the branch-circuit conductors on the line side of the controller shall not be less than 125 ...
(D) Equipment for General Use, Part-Winding Motor
For a part-winding connected motor, the ampacity of the branch-circuit conductors on the line side of the controller shall not be less than 125 ...
430.2 Equipment for General Use, Definitions
and failure to start. Part-Winding Motors. A part-winding start induction or synchronous motor is one that is arranged for starting by first energizing ...
440.53 Equipment for General Use, Overload Relays
time circuit breakers with ratings or settings in accordance with Part III unless identified for group installation or for part-winding motors ...
440.53 Equipment for General Use, Overload Relays
time circuit breakers with ratings or settings in accordance with Part III unless identified for group installation or for part-winding motors ...