Doors, Gates, and Electric Contacts Car Enclosures
Cars shall have a car door or gate provided at each entrance equipped with a car door or gate electric contact. Car doors and/or gates shall conform to the following requirements:
- They shall be positively opened by a lever or other device attached to and operated by the door or gate.
- They shall be maintained in the open position by the action of gravity or by a restrained compression spring, or both, or by positive mechanical means.
- They shall not be readily accessible.
Related Code Sections
2.14.4.2 Electric Elevators, Door and Gate Electric Contacts and Door Interlocks
Each car door or gate shall be provided with a door or gate electric contact conforming to 2.26.2.15, 2.14.4.2.3, and 2.14.4.2.5, or a car door ...
5.3.1.8 Special Application Elevators, Car Enclosures, Car Doors and Gates, and Car Illumination
(6 in.) away from a landing. (c) Car Door or Gate Electric Contacts. Every car door or gate shall be provided with an electric contact conforming ...
5.3.1.8.2 Special Application Elevators, Car Doors and Gates
door or gate if the car is more than 150 mm (6 in.) away from a landing.
Car Door or Gate Electric Contacts. Every car door or gate shall ...
5.4.4.2 Special Application Elevators, Car Doors or Gates
A car door or gate that, when closed, will guard the opening to a height of at least 1 070 mm (42 in.) or to the height of the car enclosure ...