Backshelf Hood Commercial Kitchen Hoods
Related Code Sections
507.13 Exhaust Systems, Capacity of Hoods
Commercial food service hoods shall exhaust a minimum net quantity of air determined in accordance with this section and Sections 507.13.1 through ...
507.5 Exhaust Systems, Capacity of Hoods
Commercial food service hoods shall exhaust a minimum net quantity of air determined in accordance with this section and Sections 507.5.1 through ...
507.5 Exhaust Systems, Capacity of Hoods
Commercial food service hoods shall exhaust a minimum net quantity of air determined in accordance with this section and Sections 507.5.1 through ...
507.13.3 Exhaust Systems, Medium-Duty Cooking Appliances
of Hood CFM per linear foot of hood Backshelf/pass-over 300 Double island canopy (per side) 300 Eyebrow 250 Single island canopy 500 Wall-mounted ...
507.13.4 Exhaust Systems, Light-Duty Cooking Appliances
be determined as follows: Type of Hood CFM per linear foot of hood Backshelf/pass-over 250 Double island canopy (per side) 250 Eyebrow 250 Single ...